Drop us a message here

 Request Quote

JAY JE-190

Features of Products :

  • The panel ranges from 2 to 64 zones.
  • The panel complies with IS 2189 specification.
  • The panel has separate fire and fault indications.
  • The panel also has separate fire and common fault relay.
  • The panel comprises of a 2Amp powe supply unit.
  • Battery backup is provided along with the AC supply.
  • The panel is equipped with a 24VdC piezoelectric buzzer for fault and fire.

Technical Specification :
INTERNAL POWER SUPPLY UNIT

  • Constant potential battery charger 27.5V DC Adjustable.
  • Output Current limited to 2 A.
  • Low battery voltage monitored at 18 V DC Adjustable.
  • Battery charger monitoring for failure.
  • Mains supply monitoring for failure.
  • Mains supply input voltage range 230V AC + or – 10 %, 50 Hz.
  • Total panel quiescent current 50mA nominal.
  • Approx. Standby time 4.5 Ah Batt. 36 hrs.
  • Battery recharge time from discharge 1 Hr. approx.

INTERNAL RELAY CONTACT RATING

  • Fire Relay 5 Amp. S.P. 240 V DC.
  • Common fault relay 5 Amp. S.P. 240 V DC.
  • Aux. Fire relay 5 Amp. S.P. 240 V AC.


Panel Indications :

  • System ON Green LED - System normal.
  • Common Fault Amber LED – Internal buzzer will sound intermittently.
  • Common Fire Red LED - Detector activated.
  • Zone fault Amber LED – Indicates zone wiring and detector faults.
  • Zone fire Red LED – indicates zone where fire has been detected.
  • AC fail Amber LED – Indicates loss of mains.
  • DC fail Amber LED – Indicates battery fault.
  • Batt. Low Amber LED – Indicates battery supply below 18V DC

External Controls :

  • Sound : To sound external as well as internal sounders.
  • Silence : To silence external as well as internal sounders.
  • Reset : Lamp test & resets the panels.
  • Isolate : The zone to add/clean detectors.
  • Test : International standard walk test.