Jay JE-1141

Features of Products :

  • The panel ranges from 2 to 64 zones.
  • The panel complies with IS 2189 specification.
  • The panel has separate fire and fault indications.
  • The panel also has separate fire and common fault relay.
  • The panel comprises of a 4Amp powe supply unit.
  • Battery backup is provided along with the AC supply.

Technical Specification :
INTERNAL POWER SUPPLY UNIT

  • Constant potential battery charger 14.5V DC.
  • Output Current limited to 3 A.
  • Mains supply input voltage range 230V AC + or – 10 %, 50 Hz.
  • Total panel quiescent current 50mA nominal.
  • Approx. Standby time 4.5 Ah Batt. 24 hrs.
  • Battery recharge time from discharge 3 Hr. approx.

INTERNAL RELAY CONTACT RATING

  • Fire Relay 5 Amp. S.P. 240 V DC.


Panel Indications :

  • System ON Green LED - System normal.
  • Fire Red LED – MCP/Detector activated.
  • Zone fault Amber LED – Indicates zone wiring detector fault.
  • Zone fire Red LED – indicates zone where fire has been detected.

External Controls :

  • Sound : To sound external as well as internal sounders.
  • Silence : To silence external as well as internal sounders.
  • Reset : Lamp test & resets the panels.

Operating Temprature :

  • 10- 49 degree C

Material :

  • M.S. POWDER COATED.

Cabling :

  • Four wire to be looped.